- Applies to appliances holding 15 lbs or more of HFC refrigerant (or an HFC substitute above 53 GWP) — compliance date January 1, 2026.
- Residential and light commercial AC / heat pump equipment is excluded.
- Leak-rate triggers: 10% comfort cooling, 20% commercial refrigeration, 30% industrial process refrigeration.
- Over the limit? Repair within 30 days, verify the fix, and keep records for 3 years.
Most building owners know the EPA has been tightening rules on refrigerants. What many don't realize is that the agency's Emissions Reduction and Reclamation (ER&R) program — finalized in October 2024 — put real compliance duties on owners and operators of commercial HVAC and refrigeration equipment starting January 1, 2026. Here's what it means for a typical San Antonio office, restaurant, retail center or plant.
Does it apply to your equipment?
The leak-repair requirements cover appliances with a full charge of 15 pounds or more of a refrigerant that contains an HFC, or an HFC substitute with a global warming potential above 53. In practice that pulls in many larger rooftop units, split systems serving commercial space, chillers, supermarket racks, walk-in coolers and process cooling equipment.
Residential and light commercial air conditioning and heat pump equipment is excluded, as are appliances running ultra-low-GWP substitutes (GWP 53 or below).
The leak-rate thresholds
| Appliance type | Leak rate that triggers repair | Inspection schedule |
|---|---|---|
| Comfort cooling (RTUs, chillers for building cooling) & other | 10% | Annual |
| Commercial refrigeration | 20% | Annual (15–499 lbs) · Quarterly (500+ lbs) |
| Industrial process refrigeration | 30% | Annual (15–499 lbs) · Quarterly (500+ lbs) |
The leak rate must be calculated every time refrigerant is added, using either the annualizing or rolling-average method. "Topping off" a unit every summer without documenting it is exactly the habit this rule targets.
What happens when a unit is over the limit
- Repair within 30 days (120 days if an industrial process shutdown is required). The repair must bring the leak rate below the threshold.
- Verify the repair with both an initial and a follow-up verification test.
- Or plan to retrofit / retire — if you choose not to repair, or the unit still leaks after repairs, a written retrofit or retirement plan is due within 30 days, with the work generally completed within one year.
- Report chronic leakers. Appliances that leak 125% or more of their full charge in a calendar year must be reported to EPA by March 1 of the following year.
Some owners may also be required to install automatic leak detection (ALD), and ALD can be used as a compliance option in place of periodic leak inspections.
Records: the part most owners miss
Required records must be kept for three years, paper or electronic. That means each service ticket where refrigerant is added should show the appliance, the amount added, the calculated leak rate and any repair and verification test. If your current service provider hands you a carbon copy that just says "added 4 lbs," you have a gap.
How we handle it for commercial clients
Pharis Crane LLC builds a refrigerant log for each covered appliance under a maintenance agreement — charge size, every addition, leak-rate calculation, repair and verification tests — so the paperwork exists before anyone asks for it.
Get a commercial compliance walk-through →Bottom line
If a unit on your roof needs refrigerant every season, it's no longer just a maintenance cost — it's a documentation obligation. Get an inventory of which appliances are over 15 lbs, start logging every addition, and fix chronic leakers rather than feeding them.
This article is general information, not legal advice. Binding requirements are in 40 CFR 84.106 and subpart C of part 84.